Anti-pollution line post insultors are used to support and insulate conductors on the overhead high-voltage transmission line in polluted areas .It with big diameter, large creepage distance ,great self -clean function and strong resistance to pollution ,specially serving in droughty ,rainless and windy areas .
Main Particulars and Dimensions:
Type | 57-1 | 57-2 | 57-3 | 57-4 | 57-5 | 57-6 | |
Figure NO. | 1 | 2 | 3 | 4 | 5 | 6 | |
Creepage Distance mm | 356 | 559 | 737 | 1016 | 1143 | 6 | |
Dry Arcing Distance mm | 165 | 241 | 311 | 368 | 438 | 1364 | |
Cantilever Strength KN | 12.5 | 12.5 | 12.5 | 12.5 | 12.5 | 489 | |
Power Frequency Flashover Voltage | DRY KV | 70 | 100 | 125 | 140 | 160 | 12.5 |
Wet kv | 50 | 70 | 95 | 110 | 130 | 180 | |
Critical Impulse Flashover Voltage | Positive KV | 120 | 160 | 200 | 230 | 265 | 150 |
Negative KV | 155 | 205 | 260 | 340 | 380 | 300 | |
Radio-influence-voltage Data | Test Voltage to ground | 15 | 22 | 30 | 44 | 44 | 44 |
Max.RIV at 1MHz | 100 | 100 | 200 | 200 | 200 | 200 | |
Net weight kg | 5.2 | 9.0 | 11.0 | 18 | 18 | 20.5 | |
Applicable standard | ANSI |
Main Particulars and Dimensions:
Type | 57-11 | 57-12 | 57-13 | 57-14 | 57-15 | 57-16 | |
Figure NO. | 1 | 2 | 3 | 4 | 5 | 6 | |
Creepage Distance mm | 356 | 559 | 737 | 1016 | 1143 | 1364 | |
Dry Arcing Distance mm | 165 | 241 | 311 | 368 | 438 | 489 | |
Cantilever Strength KN | 12.5 | 12.5 | 12.5 | 12.5 | 12.5 | 12.5 | |
Power Frequency Flashover Voltage | DRY KV | 70 | 100 | 125 | 140 | 160 | 180 |
Wet kv | 50 | 70 | 95 | 110 | 130 | 140 | |
Critical Impulse Flashover Voltage | Positive KV | 120 | 160 | 200 | 230 | 265 | 300 |
Negative KV | 155 | 205 | 260 | 340 | 380 | 390 | |
Radio-influence-voltage Data | Test Voltage to ground | 15 | 22 | 30 | 44 | 44 | 44 |
Max.RIV at 1MHz | 100 | 100 | 200 | 200 | 200 | 200 | |
Net weight kg | 6.8 | 10 | 11.8 | 15.9 | 18.6 | ||
Applicable standard | ANSI |
Type | 57-21 | 57-22 | 57-23 | 57-24 | 57-25 | 57-26 | |
Figure NO. | 1 | 2 | 3 | 4 | 5 | 6 | |
Creepage Distance mm | 356 | 559 | 737 | 1016 | 1143 | 1364 | |
Dry Arcing Distance mm | 165 | 241 | 311 | 368 | 438 | 489 | |
Cantilever Strength KN | 12.5 | 12.5 | 12.5 | 12.5 | 12.5 | 12.5 | |
Power Frequency Flashover Voltage | DRY KV | 70 | 100 | 125 | 140 | 160 | 180 |
Wet kv | 50 | 70 | 95 | 110 | 130 | 140 | |
Critical Impulse Flashover Voltage | Positive KV | 120 | 160 | 200 | 230 | 265 | 300 |
Negative KV | 155 | 205 | 260 | 340 | 380 | 390 | |
Radio-influence-voltage Data | Test Voltage to ground | 15 | 22 | 30 | 44 | 44 | 44 |
Max.RIV at 1MHz | 100 | 100 | 200 | 200 | 200 | 200 | |
Net weight kg | 6.8 | 10 | 11.8 | 15.9 | 18.6 | ||
Applicable standard | ANSI |